Comfort Management, display, product, Wall Panels

iSMA-B-SP

iSMA-B-SP

Basic wall panel with potentiometer, built-in temperature sensor, push button and status LED.

Cost-effective Wall Panel
iSMA-B-SP is a wall panel with a potentiometer, status LED, function button, and built-in temperature sensor. The device is designed for those who are looking for a cost-effective solution. Compact size and clear style make the device friendly to architects and building owners.

Seamless Configuration with FCU Controller
iSMA-B-SP is ready to use with FCU controllers without a need for any configuration. Wall panel connected with FCU controller creates a cost-effective solution for comfort management and energy saving.

Technical Specification

Temperature Sensor
Type: 10k NTC
Range: 0-50°C
Accuracy: +/- 0.5°C
Resolution: +/- 0.1°C

Potentiometer
Type: 10k, linear
Tolerance: ±20%

LED Diode
Waterclear blue

Push Button Switch
Normal open (NO)

IP20
MeasureTemperature

 

Comfort Management, display, product, Wall Panels

iSMA-B-LP-HC

iSMA-B-LP-HC

Wall panel with 2.3″ LCD display, control buttons, temperature, humidity and CO2 sensor. Available in two button versions: for FCU and custom applications.

Intuitive Management
The LP panels interact with a user on a 2.3” LCD that indicates the working status of the device and shows the real-time measurements from sensors. Four function buttons allow for setting the desired parameters.

Unlimited Configuration Possibilities
The LP panel is equipped with a special set of Modbus registers and BACnet objects that can be used by the user to freely control lights, blinds, alarms, and set occupancy statuses that come from the BMS system, with the possibility of displaying statuses with the display icons.

Ease of Installation and Configuration
Suitable for surface and flush mounting, the LP panel offers an effortless configuration using network protocols or a built-in USB port, even without an external power supply.

Multiprotocol Interface
The LP panel is factory-equipped with the two most popular open communication protocols, Modbus and BACnet, which are selectable using a DIP switch.

Ultimate Flexibility
The LP panels are available in two body colors, black or white, and with a set of temperature, CO2, and humidity sensors in different configurations, depending on the selected model. The iSMA-B-LP-HC version is equipped with temperature, humidity and CO2 sensor.

Technical Specification

Hardware Specification
Built-in 2.3” LCD
Four function buttons
RS485 interface
mini USB type B interface
DIP switches for configuration

Temperature sensor
Range: 0-50°C
Accuracy: +/- 0.5°C
Resolution: +/- 0.1°C

Humidity Sensor
Range: 0-100% RH
Accuracy: +/- 2% RH in range 20 – 80% RH
Resolution: +/- 1% RH

CO2 Sensor
Range: 400-2000 ppm
Accuracy: +/- 3% of reading
Stability: < 2%

Communication
BACnet MS/TP
Modbus RTU/ASCII
Free software iSMA Tool & iSMA Configurator

Power Supply
24 V DC ± 20%
24 V AC ± 20%

Power supply24 V AC, 24 V DC
Controller typeConfigurable
IP20
Communication protocolBACnet MS/TP, Modbus RTU/ASCII
MeasureRelative Humidity, Temperature, CO2

 

Comfort Management, display, product, Wall Panels

iSMA-B-LP-H

iSMA-B-LP-H

Wall panel with 2.3″ LCD display, control buttons, temperature and humidity sensor. Available in two button versions: for FCU and custom applications.

Intuitive Management
The LP panels interact with a user with a 2.3” LCD that indicates the working status of the device and shows the real-time measurements from sensors. Four function buttons allow for setting the desired parameters.

Unlimited Configuration Possibilities
The LP panel is equipped with a special set of Modbus registers and BACnet objects that can be used by the user to freely control lights, blinds, alarms, and set occupancy statuses that come from the BMS system, with the possibility of displaying statuses with the display icons.

Ease of Installation and Configuration
Suitable for surface and flush mounting, the LP panel offers an effortless configuration using network protocols or a built-in USB port, even without an external power supply.

Multiprotocol interface
The LP panel is factory-equipped with the two most popular open communication protocols, Modbus and BACnet, which are selectable using a DIP switch.

Ultimate flexibility
The LP panels are available in two body colors, black or white, and with a set of temperature, CO2, and humidity sensors in different configurations, depending on the selected model. The iSMA-B-LP-H version is equipped with temperature and humidity sensors.

Technical Specification

Hardware Specification
Built-in 2.3” LCD
Four function buttons
RS485 interface
mini USB type B interface
DIP switches for configuration

Temperature Sensor
Range: 0-50°C
Accuracy: +/- 0.5°C
Resolution: +/- 0.1°C

Humidity Sensor
Range: 0-100% RH
Accuracy: +/- 2% RH in range 20-80% RH
Resolution: +/- 1% RH

Communication
BACnet MS/TP
Modbus RTU/ASCII
Free software iSMA Tool & iSMA Configurator

Power Supply
24 V DC ± 20%
24 V AC ± 20%

Power supply24 V AC, 24 V DC
Controller typeConfigurable
IP20
Communication protocolBACnet MS/TP, Modbus RTU/ASCII
MeasureRelative Humidity, Temperature

 

Comfort Management, display, product, Wall Panels

iSMA-B-LP-C

iSMA-B-LP-C

Wall panel with 2.3″ LCD display, control buttons, temperature and CO2 sensor. Available in two button versions: for FCU and custom applications.

Intuitive Management
The LP panels interact with a user on a 2.3” LCD that indicates the working status of the device and shows the real-time measurements from sensors. Four function buttons allow for setting the desired parameters.

Unlimited Configuration Possibilities
The LP panel is equipped with a special set of Modbus registers and BACnet objects that can be used by the user to freely control lights, blinds, alarms, and set occupancy statuses that come from the BMS system, with the possibility of displaying statuses with the display icons.

Ease of Installation and Configuration
Suitable for surface and flush mounting, the LP panel offers an effortless configuration using network protocols or a built-in USB port, even without an external power supply.

Multiprotocol Interface
The LP panel is factory-equipped with the two most popular open communication protocols, Modbus and BACnet, which are selectable using a DIP switch.

Ultimate Flexibility
The LP panels are available in two body colors, black or white, and with a set of temperature, CO2, and humidity sensors in different configurations, depending on the selected model. The iSMA-B-LP-HC version is equipped with temperature and CO2 sensors.

Technical Specification

Hardware Specification
Built-in 2.3” LCD
Four function buttons
RS485 interface
mini USB type B interface
DIP switches for configuration

Temperature Sensor
Range: 0-50°C
Accuracy: +/- 0.5°C
Resolution: +/- 0.1°C

CO2 Sensor
Range: 400-2000 ppm
Accuracy: +/- 3% of reading
Stability: < 2%

Communication
BACnet MS/TP
Modbus RTU/ASCII
Free software iSMA Tool & iSMA Configurator

Power Supply
24 V DC ± 20%
24 V AC ± 20%

Power supply24 V AC, 24 V DC
Controller typeConfigurable
IP20
Communication protocolBACnet MS/TP, Modbus RTU/ASCII
MeasureTemperature, CO2
Comfort Management, display, product, Wall Panels

iSMA-B-LP

iSMA-B-LP

Wall panel with 2.3″ LCD display, control buttons, and temperature sensor. Available in two button versions: for FCU and custom applications.

Intuitive Management
The LP panels interact with a user on a 2.3” LCD that indicates the working status of the device and shows the real-time measurements from sensors. Four function buttons allow for setting the desired parameters.

Unlimited Configuration Possibilities
The LP panel is equipped with a special set of Modbus registers and BACnet objects that can be used by the user to freely control lights, blinds, alarms, and set occupancy statuses that come from the BMS system, with the possibility of displaying statuses with the display icons.

Ease of Installation and Configuration
Suitable for surface and flush mounting, the LP panel offers an effortless configuration using network protocols or a built-in USB port, even without an external power supply.

Multiprotocol Interface
The LP panel is factory-equipped with the two most popular open communication protocols, Modbus and BACnet, which are selectable using a DIP switch.

Ultimate Flexibility
The LP panels are available in two body colors, black or white, and with a set of temperature, CO2, and humidity sensors in different configurations, depending on the selected model. The iSMA-B-LP version is equipped with a temperature sensor.

Technical Specification

Hardware Specification
Built-in 2.3” LCD
Four function buttons
RS485 interface
mini USB type B interface
DIP switches for configuration

Temperature Sensor
Range: 0-50°C
Accuracy: +/- 0.5°C
Resolution: +/- 0.1°C
Communication
BACnet MS/TP
Modbus RTU/ASCII
Free software iSMA Tool & iSMA Configurator

Power Supply
24 V DC ± 20%
24 V AC ± 20%

Power supply24 V AC, 24 V DC
Controller typeConfigurable
IP20
Communication protocolBACnet MS/TP, Modbus RTU/ASCII
MeasureTemperature

 

Comfort Management, controller, Lights & Blinds, product

iSMA-B-2D1B-WD

iSMA-B-2D1B-WD

DALI lighting and blind/shutter configurable controller with Modbus RTU communication. Equipped with Wieland Connectors.

Experience our Light and Blind Controller
To minimize time and simplify the commissioning process, the 2D1B-WD controller is delivered with a built-in application, which supports the most popular light and blind/shutter motor control in a single space in a building. The controller is dedicated to controlling two separate DALI light areas with up to 32 DALI ballasts.

2 Special Inputs
Built-in two special inputs are designed to control the light via connected motion sensors or presence detectors.

4 Digital Inputs
The controller is equipped with four dry contact inputs onboard:
2 digital inputs for control of the light by connected monostable or bistable switches,
2 digital inputs for double switch connection for control blind/shutter up and down movement.

2 Light Outputs
The device is equipped with two fuse protected light outputs 230 V AC, with a maximum 4 A load. The outputs can work in two modes defined via DIP switches: DALI or ON/OFF.

1 Blind Output
The 2D1B-WD controller has one double blind output dedicated for a blind/shutter control. The double 230 V AC blind output allows for controlling the up and down movement of the blind/shutter.

24 V DC Power Supply Output
The device is equipped with a 24 V DC output for providing power for motion sensors or presence detectors, which demand an additional supply.

Open Communication
The 2D1B-WD controller is equipped with RS485 interfaces with open protocol Modbus RTU/ASCII. You can connect up to 128 devices on one bus.

Simplified Configuration and Commissioning Process
The 2D1B-WD controller is ready for operation out of the box, you just have to configure the controller using built-in DIP switches.

Technical Specification

Hardware Specification
ARM Cortex-M4 processor
RS485 interface
2 separate DALI interfaces – supplying power for up to 16 DALI ballasts
mini USB type B interface
DIP switches for configuration
Status LED indicators
DIN rail mounted

Inputs
2 Special Inputs (SI)
Dry contact input dedicated for motion or presence sensors

4 Digital Inputs (DI)
Dry contact inputs
2 digital inputs for light control
2 digital inputs for blind/shutter control

Outputs
2 light outputs, max. 4 A
1 motor output, 230 V AC max. 1.5 A
1 power supply output, 24 V DC max. 80 mA

Communication
Modbus RTU/ASCII
DALI

Power Supply
230 V AC

Power supply230 V AC
Digital inputs4
Inputs typeDigital, Special
Outputs typeDigital
Controller typeConfigurable
IP40
Communication protocolDALI, Modbus RTU/ASCII

 

Comfort Management, controller, Lights & Blinds, product

iSMA-B-2D1B

iSMA-B-2D1B

DALI lighting and blind/shutter configurable controller with Modbus RTU communication.

Experience our Light and Blind Controller
To minimize time and simplify the commissioning process, the 2D1B controller is delivered with a built-in application, which supports the most popular light and blind/shutter motor control in a single space in a building. The controller is dedicated to controlling two separate DALI light areas with up to 32 DALI ballasts.

2 Special Inputs
Built-in two special inputs are designed to control the light via connected motion sensors or presence detectors.

4 Digital Inputs
There are onboard four dry contact inputs:
2 digital inputs for control of the light by connected monostable or bistable switches
2 digital inputs for double switch connection to control blind/shutter up and down movement.

2 Light Outputs
The device is equipped with two fuse protected light outputs 230 V AC, with a maximum 4 A load. The outputs can work in two defined via DIP switches modes: DALI or ON/OFF.

1 Blind Output
The 2D1B controller has one double blind output dedicated for a blind/shutter control. The double 230 V AC blind output allows for controlling the up and down movement of the blind/shutter.

24 V DC Power Supply Output
The device is equipped with a 24 V DC output for providing power for motion sensors or presence detectors, which demand an additional supply.

Open Communication
The 2D1B controller is equipped with RS485 interfaces with open protocol Modbus RTU/ASCII. You can connect up to 128 devices on one bus.

Simplified Configuration and Commissioning Process
The 2D1B controller is ready for operation out of the box, you just have to configure the controller using built-in DIP switches.

Technical Specification

Hardware Specification
ARM Cortex-M4 processor
RS485 interface
2 separate DALI interfaces – supplying power for up to 16 DALI ballasts
mini USB type B interface
DIP switches for configuration
Status LED indicators
DIN rail mounted

Inputs
2 Special Inputs (SI)
Dry contact input dedicated for motion or presence sensors

4 Digital Inputs (DI)
Dry contact inputs
2 digital inputs for light control
2 digital inputs for blind/shutter control

Outputs
2 light outputs, max. 4 A
1 motor output, 230 V AC max. 1.5 A
1 power supply output, 24 V DC max. 80 mA

Communication
Modbus RTU/ASCII
DALI

Power Supply
230 V AC

More Information
Power supply230 V AC
Digital inputs4
Inputs typeDigital, Special
Controller typeConfigurable
IP40
Communication protocolDALI, Modbus RTU/ASCII

 

Comfort Management, controller, Lights & Blinds, product

iSMA-B-2D-WD

iSMA-B-2D-WD

DALI lighting configurable controller with Modbus RTU communication. Equipped with Wieland Connectors.

Experience our Light Controller
To minimize time and simplify the commissioning process, the 2D-WD controller is delivered with a built-in application, which supports the most popular light control applications in a single space in a building. The controller is dedicated to controlling two separate DALI light areas with up to 32 DALI ballasts.

2 Special Inputs
Built-in two special inputs are designed to control the light via connected motion sensors or presence detectors. Additionally, special inputs may read the light level intensity from standardized sensors.

4 Digital Inputs and Outputs

The controller is equipped with four dry contact inputs onboard:
2 digital inputs for control of the light by connected monostable or bistable switches
2 digital inputs for occupancy sensors
2 light outputs
The device is equipped with two fuse protected light outputs 230 V AC, with a maximum 4 A load. The outputs can work in two modes defined via DIP switches: DALI or ON/OFF.

24 V DC Power Supply Output
The device is equipped with a 24 V DC output for providing power for motion sensors or presence detectors, which demand an additional supply.

Open Communication
The 2D-WD controller is equipped with RS485 interfaces with open protocol Modbus RTU/ASCII. You can connect up to 128 devices on one bus.

Simplified Configuration and Commissioning Process
The 2D-WD controller is ready for operation out of the box, you just have to configure the controller using built-in DIP switches.

Technical Specification

Hardware Specification
ARM Cortex-M4 processor
RS485 interface
2 separate DALI interfaces – supplying power for up to 16 DALI ballasts
mini USB type B interface
DIP switches for configuration
Status LED indicators
DIN rail mounted

Inputs
2 Special Inputs (SI)
Dry contact input dedicated for motion, presence, or light level intensity sensors

4 Digital Inputs (DI)
Dry contact inputs
2 digital inputs for light control
2 digital inputs for occupancy sensor

Outputs
2 light outputs, max. 4 A
1 power supply output, 24 V DC max. 80 mA

Communication
Modbus RTU/ASCII
DALI

Power Supply
230 V AC

Power supply230 V AC
Digital inputs4
Inputs typeDigital, Special
Outputs typeDigital
Controller typeConfigurable
IP40
Communication protocolDALI, Modbus RTU/ASCII

 

Comfort Management, controller, Lights & Blinds, product

iSMA-B-2D

iSMA-B-2D

DALI lighting configurable controller with Modbus RTU communication.

Experience our Light Controller
To minimize time and simplify the commissioning process, the 2D controller is delivered with a built-in application, which supports the most popular light control applications in a single space in a building. The controller is dedicated to controlling two separate DALI light areas with up to 32 DALI ballasts.

2 Special Inputs
Built-in two special inputs are designed to control the light via connected motion sensors or presence detectors. Additionally, special inputs may read the light level intensity from standardized sensors.

4 Digital Inputs and Outputs

The controller is equipped with four dry contact inputs onboard:
2 digital inputs for control of the light by connected monostable or bistable switches
2 digital inputs for occupancy sensors
2 light outputs
The device is equipped with two fuse-protected light outputs 230 V AC, with a maximum 4 A load. The outputs can work in two modes defined via DIP switches: DALI or ON/OFF.

24 V DC Power Supply Output
The device is equipped with a 24 V DC output for providing power for motion sensors or presence detectors, which demand an additional supply.
Open Communication
The 2D controller is equipped with RS485 interfaces with open protocol Modbus RTU/ASCII. You can connect up to 128 devices on one bus.

Simplified Configuration and Commissioning Process
The 2D controller is ready for operation out of the box, you just have to configure the controller using built-in DIP switches.

Technical Specification

Hardware Specification
ARM Cortex-M4 processor
RS485 interface
2 separate DALI interfaces – supplying power for up to 16 DALI ballasts
mini USB type B interface
DIP switches for configuration
Status LED indicators
DIN rail mounted

Inputs
2 Special Inputs (SI)
Dry contact input dedicated for motion, presence, or light level intensity sensors

4 Digital Inputs (DI)
Dry contact inputs
2 digital inputs for light control
2 digital inputs for occupancy sensor

Outputs
2 light outputs, max. 4 A
1 power supply output, 24 V DC max. 80 mA

Communication
Modbus RTU/ASCII
DALI

Power Supply
230 V AC

Power supply230 V AC
Digital inputs4
Inputs typeDigital, Special
Outputs typeDigital
Controller typeConfigurable
IP40
Communication protocolDALI, Modbus RTU/ASCII

 

Comfort Management, controller, product, Zone Controllers

RAC18-IP

RAC18-IP

Freely programable Room Application Controller RAC18 with 4UI, 4DI, 5DO, 3AO, 2TO, 1xRS485, 1xUSB and 2 fail-safe protected Ethernet ports. Power supply 24 V AC/DC.

Room and Zone Management
The RAC18-IP controller is a multifunctional device providing comfort in a single room or a zone in the building. Onboard 18 I/O’s with Ethernet and serial ports make the controller a versatile system for comfort management, light and blind control, integration and monitoring.

High-end Technology at the Edge
Powerful, IoT ready nano EDGE ENGINE allows unprecedented capabilities for a microcontroller-based device. Take advantage of a time-saving automatic BACnet exposure, real-time programming, and cloud connectivity.

Openness and Reliability
Take advantage of the IP connectivity with open protocols like MQTT, BACnet, and Modbus, and ensure the highest energy efficiency for your building with any supervisory system. Daisy-chained RAC18-IP controllers are protected by a unique fail-safe system on each Ethernet port to provide maximum reliability.

Seamless Programming and Maintenance
Maintain and program your device from anywhere in real-time with a dedicated, free of charge tool. Easy replacement process with system and user data saved on a removable SD card.

4 Universal Inputs
Support for over 20 types of temperature sensors and voltage, resistance, current, and dry contact measurements on each universal input.

4 Digital Inputs
Dry contact inputs – made for monitoring. 100 Hz fast pulse counter with override function saves the real-time values to the non-volatile memory of the controller.

5 Digital Outputs
Digital outputs equipped with normally open 3A relays allow for direct control without additional relays.

3 Analog Outputs
0-10 V DC control with 10 mA accuracy, PWM modes, and a maximum load of up to 20 mA to power external relays makes the output suitable for a variety of scenarios.

2 Triac Outputs
The controller is equipped with two triac outputs that can be used for heating and cooling thermal valve actuators. Outputs can be connected to actuators with a 24 V AC power supply.
Triac outputs can work as typical binary outputs for binary temperature control or with PWM modulation up to 0.5 A load.

Technical Specification

Hardware Specification
Highest performing ARM Cortex-M7
Built-in real-time clock (RTC)
RS485 interface
2 fail-safe protected Ethernet interfaces with a built-in switch
USB type C interface
microSD card
18 I/Os onboard
Status LED indicators
DIN-rail mounted

Inputs
4 Universal Inputs (UI)
Temperature input: 10K3A1, 10K4A1, Carel 10K, 20K6A1, 2.2K3A1, 3K3A1, 30K6A1, SIE1, TAC1, SAT1, Pt1000, Ni1000 0C, Ni 1000 20C, Ni1000 LG 2.
Resistive input 0-1000 kΩ
Voltage input 0-10 V DC
Current input 0-20 mA
Dry contact input

4 Digital Inputs (DI)
Dry contact inputs
Fast pulse counter up to 100 Hz saved in the EEPROM memory

Outputs
5 Digital Outputs (DO)
NO relay output
Resistive load max. 3 A @ 230 V AC/30 V DC
Inductive load max. 75 VA @ 230 V AC/30 W @ 30 V DC

3 Analog Outputs (AO)
0-10 V DC output with maximum load up to 20 mA
PWM: 0.01 Hz, 0.1 Hz, 1 Hz, 10 Hz, 100 Hz

2 Triac Outputs (TO)
0.5 A @ 24 V AC for heating and cooling actuators
PWM: 0.01 Hz, 0.1 Hz, 1 Hz, 10 Hz, 100 Hz

Communication
BACnet IP
Modbus RTU/ASCII client
Modbus TCP/IP server
Free software: iC Tool

Power Supply
24 V DC ± 20%
24 V AC ± 20%

Power supply24 V AC, 24 V DC
Analog outputs3
Digital outputs5
Digital inputs4
Universal inputs4
Inputs typeUniversal, Digital
Outputs typeAnalog, Triac, Digital
Controller typeProgrammable
IP20