product, Sensors, Temperature and Humidity

TUTA35 NTC

TUTA35 NTC

Room Relative Humidity and Temperature sensor
Output signal 0 ÷ 10 Vdc and 4 to 20 mA with auto-detection
Degree of protection IP65

The relative humidity transmitters, also available combined with temperature sensor, are used in air conditioning system for the measurement of relative humidity. They measure the relative humidity value to be measured by a capacitive sensitive element whose signal, suitably linearized and amplified, is transformed into a voltage signal (0..10 V) or current (4..20 mA ) at the terminals of output.
in models with temperature sensor the sensing element is constituted by a resistance NTC (10 kΩ).

MeasureRelative Humidity, Temperature
ApplicationRoom
InstallationWall
Sensing elementNTC 10 kOhm
T Fluid min [°C]0
T Fluid max [°C]50
Rh0-95%
Power supply24 V AC, 24 V DC
IP30
Output signal0÷10 Vdc, 4÷20 mA

 

product, Sensors, Temperature and Humidity

TUTD32 NTC

TUTD32 NTC

Temperature and relative humidity transmitter for duct
Probe length 200 mm
Output signal 0 ÷ 10 Vdc / Ohm (temp. Balco) (3 + 2 wires)
IP55 protection rating

The relative humidity transmitters, also available combined with temperature sensor, are used in air conditioning system for the measurement of relative humidity. They measure the relative humidity value to be measured by a capacitive sensitive element whose signal, suitably linearized and amplified, is transformed into a voltage signal (0..10 V) or current (4..20 mA ) at the terminals of output.
in models with temperature sensor the sensing element is constituted by a resistance Balco, NTC (10 kΩ) or PTC (1 kΩ).

 
MeasureRelative Humidity, Temperature
ApplicationDuct
InstallationDuct
Sensing elementNTC 10 kOhm
T Fluid min [°C]0
T Fluid max [°C]50
Rh0-95%
Power supply15 to 25 V DC, 24 V AC
Output signal0÷10 Vdc

 

product, Sensors, Temperature and Humidity

TUTD32N10 NTC

TUTD32N10 NTC

Temperature and relative humidity transmitter for duct
Probe length 200 mm
Output signal 0 ÷ 10 Vdc / Ohm (temp. NTC 10kOhm) (3 + 2 wires)
IP55 protection rating

The relative humidity transmitters, also available combined with temperature sensor, are used in air conditioning system for the measurement of relative humidity. They measure the relative humidity value to be measured by a capacitive sensitive element whose signal, suitably linearized and amplified, is transformed into a voltage signal (0..10 V) or current (4..20 mA ) at the terminals of output.
in models with temperature sensor the sensing element is constituted by a resistance Balco, NTC (10 kΩ) or PTC (1 kΩ).

MeasureRelative Humidity, Temperature
ApplicationDuct
InstallationDuct
Sensing elementNTC 10 kOhm
T Fluid min [°C]0
T Fluid max [°C]50
Rh0-95%
Power supply15 to 25 V DC, 24 V AC
Output signal0÷10 Vdc

 

product, Sensors, Temperature and Humidity

TUTD32P1

TUTD32P1

Temperature and relative humidity transmitter for duct
Probe length 200 mm
Output signal 0 ÷ 10 Vdc / Ohm (temp.1kOhm PTC) (3 + 2 wires)
IP55 protection rating

The relative humidity transmitters, also available combined with temperature sensor, are used in air conditioning system for the measurement of relative humidity. They measure the relative humidity value to be measured by a capacitive sensitive element whose signal, suitably linearized and amplified, is transformed into a voltage signal (0..10 V) or current (4..20 mA ) at the terminals of output.
in models with temperature sensor the sensing element is constituted by a resistance Balco, NTC (10 kΩ) or PTC (1 kΩ).

MeasureRelative Humidity, Temperature
ApplicationDuct
InstallationDuct
Sensing elementPTC 1 kOhm
T Fluid min [°C]0
T Fluid max [°C]50
Rh0-95%
Power supply15 to 25 V DC, 24 V AC
Output signal0÷10 Vdc

 

product, Sensors, Temperature and Humidity

TUTD34 NTC

TUTD34 NTC

Temperature and relative humidity transmitter for duct
Probe length 230 mm
Output signal 0 ÷ 10 Vdc / Ohm (temp.) (3 + 2 wires)
Degree of protection IP65

The relative humidity transmitters, also available combined with temperature sensor, are used in air conditioning system for the measurement of relative humidity. They measure the relative humidity value to be measured by a capacitive sensitive element whose signal, suitably linearized and amplified, is transformed into a voltage signal (0..10 V) or current (4..20 mA ) at the terminals of output.
In models with temperature sensor the sensing element is constituted by a resistance NTC (5 kΩ).

MeasureRelative Humidity, Temperature
ApplicationDuct
InstallationDuct
Sensing elementNTC 5 kOhm
T Fluid min [°C]0
T Fluid max [°C]50
Rh0-95%
Power supply15 to 35 V DC, 24 V AC
IP65
Output signal0÷10 Vdc, 4÷20 mA