DALI lighting and blind/shutter configurable controller with Modbus RTU communication. Equipped with Wieland Connectors.
Experience our Light and Blind Controller
To minimize time and simplify the commissioning process, the 2D1B-WD controller is delivered with a built-in application, which supports the most popular light and blind/shutter motor control in a single space in a building. The controller is dedicated to controlling two separate DALI light areas with up to 32 DALI ballasts.
2 Special Inputs
Built-in two special inputs are designed to control the light via connected motion sensors or presence detectors.
4 Digital Inputs
The controller is equipped with four dry contact inputs onboard:
2 digital inputs for control of the light by connected monostable or bistable switches,
2 digital inputs for double switch connection for control blind/shutter up and down movement.
2 Light Outputs
The device is equipped with two fuse protected light outputs 230 V AC, with a maximum 4 A load. The outputs can work in two modes defined via DIP switches: DALI or ON/OFF.
1 Blind Output
The 2D1B-WD controller has one double blind output dedicated for a blind/shutter control. The double 230 V AC blind output allows for controlling the up and down movement of the blind/shutter.
24 V DC Power Supply Output
The device is equipped with a 24 V DC output for providing power for motion sensors or presence detectors, which demand an additional supply.
Open Communication
The 2D1B-WD controller is equipped with RS485 interfaces with open protocol Modbus RTU/ASCII. You can connect up to 128 devices on one bus.
Simplified Configuration and Commissioning Process
The 2D1B-WD controller is ready for operation out of the box, you just have to configure the controller using built-in DIP switches.
Â
Technical Specification
Â
Hardware Specification
ARM Cortex-M4 processor
RS485 interface
2 separate DALI interfaces – supplying power for up to 16 DALI ballasts
mini USB type B interface
DIP switches for configuration
Status LED indicators
DIN rail mounted
Inputs
2 Special Inputs (SI)
Dry contact input dedicated for motion or presence sensors
4 Digital Inputs (DI)
Dry contact inputs
2 digital inputs for light control
2 digital inputs for blind/shutter control
Outputs
2 light outputs, max. 4 A
1 motor output, 230 V AC max. 1.5 A
1 power supply output, 24 V DC max. 80 mA
Communication
Modbus RTU/ASCII
DALI
Power Supply
230 V AC
Power supply | 230 V AC |
---|---|
Digital inputs | 4 |
Inputs type | Digital, Special |
Outputs type | Digital |
Controller type | Configurable |
IP | 40 |
Communication protocol | DALI, Modbus RTU/ASCII |