iSMA-B-4TO-H-IP

4TO H IP persp

Multiprotocol I/O module with 4 triac outputs, HOA switches, IP connectivity, and built-in Modbus TCP/IP to Modbus RTU/ASCII gateway.

Multiprotocol I/O Module in a Compact Size
Powerful I/O module that works as a remote I/O over IP with open protocols, BACnet IP and Modbus TCP/IP. A compact size and ease of installation allow the module to be fitted even into limited space installations.

4 Triac Outputs
Silent control of AC current with four solid-state outputs with PWM mode and up to 0.5 A load.

Manual Override Switches
Each output can be manually overridden using a dedicated hand operating switch.

Modbus TCP/IP to Modbus RTU/ASCII Gateway
Built-in Modbus gateway on the COM1 port enables integration of up to 128 Modbus slave devices to the IP layer.

Simplified Configuration and Commissioning Process
The module allows for seamless configuration over BACnet, Modbus, built-in web server or dedicated free of charge tool. The ability to be powered from a USB port facilitates local testing and a straightforward updating process.

Quality and Reliability Confirmed by Certificates
iSMA CONTROLLI is a long-standing member of the BACnet community. The experience in developing high quality products and the BTL (BACnet Test Laboratory) certification confirm the excellent performance of communication using the BACnet protocol.
Reliability of operation is confirmed by UL testing, certified by Underwriters Laboratories.


 

Technical Specification

 

Hardware Specification
Ethernet interface
RS485 interface
mini USB type B interface
Status LED indicators
DIN rail mounted

Outputs
4 Triac Outputs (TO)
0.5 A @ 24 V AC, 0.5 A @ 230 V AC
Continuous load per channel: 0.5 A (1.5 A peak 30 s)
Switching voltage: 20 to 250 V AC

Communication
BACnet IP
Modbus TCP/IP
Modbus TCP/IP to Modbus RTU/ASCII gateway
Free software iSMA Configurator
Built-in web server
Dedicated Niagara Framework modules

Power Supply
24 V DC ± 20%
24 V AC ± 20%

Outputs typeTriac
Communication protocolBACnet IP, Modbus TCP/IP, Modbus TCP/IP to Modbus RTU/ASCII Gateway
Power supply24 V AC, 24 V DC
IP40

 