Modbus I/O module with 16 digital outputs, PNP type.
Modbus I/O Module
SfAR-S-16DO gives users a possibility to send multiple signals to multiple devices, for example, to start/stop or alarm reset commands for pumps.
16 Digital Outputs
The module has 16 digital outputs (DO). Digital outputs are PNP transistor outputs, sending voltage signals. All outputs are isolated from the logic with optoisolators.
Simplified Configuration and Commissioning Process
A built-in RS485 interface allows an easy connection over the Modbus RTU/ASCII protocol. A 32-bit ARM core processor provides fast processing and communication.
The module is equipped with a set of LEDs used to indicate the status of I/Os, power supply, and RS485 communication.
Configuration of the module is carried out with our free software, the SfAR Configurator. A built-in mini USB allows for performing a primary configuration of the unit without an additional power supply.
To simplify the installation, the module has been equipped with the Quick Connector system. Using a dedicated SfAR-S-LINK cable allows for connecting up to 10 modules, which provide both RS485 communication and external power supply.
Â
Technical Specification
Â
Hardware Specification
RS485 interface
mini USB type B interface
Status LED indicators
DIN rail mounted
Quick Connector system
Outputs
16 Digital Outputs (DO)
PNP
30 V DC, 500 mA
Opto-isolated from RS485 and power supply
Communication
Modbus RTU/ASCII
Dedicated TCP/IP to Modbus RTU/ASCII gateway device, SfAR-S-ETH
Free software – SfAR Configurator
Power Supply
10-38 V DC ± 20%
10-28 V AC ± 20%
Outputs type | Digital |
---|---|
Communication protocol | Modbus RTU/ASCII |
Power supply | 10 to 28 V AC, 10 to 38 V DC |
IP | 40 |
Digital outputs | 16 |
Â